US EV charger circuit calculator

Find the breaker size, copper wire size and voltage drop for a Level 2 home EV charger, and how long it takes to charge.

The charger's maximum current, as on its label or its setting. A 48 amp charger delivers about 11.5 kW at 240 volts.

One way, in feet.

60 degrees C is the usual limit for circuits up to 100 amps unless the equipment is marked for 75.

Many inspectors require this. Some accept wire sized to the charger current with only the breaker at 125%.

Charging time

Many cars take 7 to 11.5 kW on AC.

The share of the energy from the wall that reaches the battery. 85 to 92% is typical.

Breaker size

50 amps

A 50 amps breaker with 6 AWG copper wire. Charging from the start to the target takes about 5.21 hours.

Charger power
9.6 kW
Smallest copper wire
6 AWG copper
Wire ampacity in that column
55 amps
Voltage drop over the run
0.82 %
Charging power used
9.6 kW
Time to charge
5.21 hours
  • This is a planning guide, not an electrical design. A licensed electrician must size the circuit, check the panel's capacity and pull the permit. Local rules and the edition of the code in force may differ.

How it works

A Level 2 home charger needs a breaker rated at 125% of its current, rounded up to the next standard size, so a 40 amp charger goes on a 50 amp breaker. From the charger’s current and the length of the run, the calculator also picks the smallest copper wire in the ampacity table and gives the voltage drop and the time to charge.

The electrician’s bill for a new circuit is a one-off cost. To see what room a paycheck leaves for it, use the US take-home pay calculator, and if you are paying for the installation with a loan, see what the repayments come to. If the charger is part of a new garage or workshop, the US timber span calculator gives joist and rafter spans for the framing.

The formula

breaker = 125% × charger current, rounded up to the next standard size
wire    = smallest copper size whose ampacity ≥ 125% × current (or the current)
voltage drop = 2 × 12.9 × current × one-way length ÷ circular mils of the wire
charge time  = battery kWh × (target − start) ÷ (charging kW × efficiency)
charging kW  = the smaller of the charger (volts × amps ÷ 1000) and the car's limit

The ampacities are from Table 310.16 for copper conductors in the 60 and 75 degree columns.

What each input means

A worked example

A 40 amp charger on 240 volts, 50 feet from the panel, with wire sized at 125%.

How the figures are rounded

Currents are used as entered. Voltage drop and charging time are rounded to two decimal places.

What it leaves out

Aluminum wire, wire in conduit with more than three conductors or high ambient temperatures, the panel’s spare capacity, adjustable-current chargers set below their rating, load management systems, ground-fault protection requirements, permits and the local edition of the code. The resistivity constant and circular mil values are standard published figures. This page has not been compared with the code text itself, so a licensed electrician must confirm every figure.

Common questions

Why is the breaker 125% of the charger current?

An EV charger is treated as a continuous load, which means it runs for three hours or more. The code sizes the breaker at no less than 125% of the charger's maximum current, then rounds up to the next standard size. A 40 amp charger needs a 50 amp breaker.

Does the wire have to be sized for 125% too?

Practice varies. The general rule for branch circuits applies 125% to the wire as well, and many inspectors require it. A New Jersey code opinion accepts wire sized to the charger current with only the breaker at 125%. The box above is ticked by default, which is the safer choice. Ask your local inspector.

What does the terminal rating mean?

It is the temperature the breaker and charger terminals are rated for, normally 60 degrees C for circuits of 100 amps or less unless the equipment is marked for 75. The wire is chosen from the matching column of the ampacity table.

Do I need to worry about voltage drop?

On long runs, yes. The code suggests keeping the drop on a branch circuit to about 3%. A larger wire reduces it. The calculator flags a drop over 3% and does not choose a bigger wire for you.

Is this enough to install a charger?

No. The panel must have spare capacity, which a service load calculation shows, and an electrician has to install the circuit and in most places pull a permit. Treat this as a planning check before you call one.

Sources and review

The method and any rates on this page come from:

This page gives general information for planning and discussion. It is not engineering advice and does not replace the design, calculation or inspection of a licensed professional or the approval of your local building or electrical authority. Codes differ by place and edition, and a wrong size can be unsafe. Have the result checked by a qualified person before you buy materials or start work.

Report an error on this page