US EV charger circuit calculator

The charger's maximum current, as on its label or its setting. A 48 amp charger delivers about 11.5 kW at 240 volts.

One way, in feet.

60 degrees C is the usual limit for circuits up to 100 amps unless the equipment is marked for 75.

Many inspectors require this. Some accept wire sized to the charger current with only the breaker at 125%.

Charging time

Many cars take 7 to 11.5 kW on AC.

The share of the energy from the wall that reaches the battery. 85 to 92% is typical.

Breaker size

50 amps

A 50 amps breaker with 6 AWG copper wire. Charging from the start to the target takes about 5.21 hours.

Charger power
9.6 kW
Smallest copper wire
6 AWG copper
Wire ampacity in that column
55 amps
Voltage drop over the run
0.82 %
Charging power used
9.6 kW
Time to charge
5.21 hours
  • This is a planning guide, not an electrical design. A licensed electrician must size the circuit, check the panel's capacity and pull the permit. Local rules and the edition of the code in force may differ.

Calculator by Sumverge